Wire Size for 15000W at 400V (50 Meters) → 4 mm²

Calculate electrical wire size in mm² and AWG for 12V, 24V, 120V, 230V and 400V based on power, length and voltage drop under NEC Table 310.16 and IEC 60364.

Recommended Wire Size4 mm²
Exact Theoretical Area2.61 mm²
Line Current (Amps)15.2 A
Line Power Loss68 W

Voltage Drop & Conductor Cross-Section Formulas

Regulatory Reference (USA & International): Under NFPA 70 (NEC Art. 210.19) and IEC 60364-5-52, maximum recommended voltage drop is 3% for branch circuits and 5% combined feeder + branch. Ampacity must comply with NEC Table 310.16 (75°C / 90°C copper).

Direct Current (DC) & Single-Phase AC: S = (2 × L × I × ρ) / ΔU
Three-Phase Alternating Current (400V): S = (√3 × L × I × ρ × cos φ) / ΔU

Standard Copper Wire Sizes, Ampacity & Breaker Protection (NEC / IEC)

Wire Size (mm²)Max Current PVC (A)Typical Breaker (MCB)Typical Residential / Solar Application
1.5 mm²15 A10 ALighting circuits (C1) & signaling
2.5 mm²21 A16 AGeneral power outlets (C2) & kitchen/bath (C5)
4.0 mm²27 A20 AWashing machine, dishwasher & water heater
6.0 mm²36 A25 AElectric stove, oven & medium solar inverters
10.0 mm²50 A40 AMain sub-feeders & EV charging station (Wallbox)
16.0 mm²66 A50 A / 63 AHigh-power main feeders & 24V/48V battery banks