Convert American Wire Gauge (AWG) to square millimeters (mm²). Calculate bare conductor diameter, ohmic resistance per km and IEC metric equivalent.
Standard Reference (ASTM B258 & IEC 60228): North American wire gauges follow a logarithmic geometric progression where every 3 AWG step doubles the cross-sectional area.
| AWG Gauge | Exact Area (mm²) | European Metric Size | Diámetro (mm) | Max Ampacity (75°C NEC) |
|---|---|---|---|---|
| 18 AWG | 0.823 mm² | 1.0 mm² | 1.024 mm | 7 A - 10 A |
| 16 AWG | 1.31 mm² | 1.5 mm² | 1.291 mm | 13 A |
| 14 AWG | 2.08 mm² | 2.5 mm² | 1.628 mm | 15 A - 20 A |
| 12 AWG | 3.31 mm² | 4.0 mm² | 2.053 mm | 20 A - 25 A |
| 10 AWG | 5.26 mm² | 6.0 mm² | 2.588 mm | 30 A - 35 A |
| 8 AWG | 8.37 mm² | 10.0 mm² | 3.264 mm | 50 A |
| 6 AWG | 13.30 mm² | 16.0 mm² | 4.115 mm | 65 A |
| 4 AWG | 21.15 mm² | 25.0 mm² | 5.189 mm | 85 A |
| 2 AWG | 33.62 mm² | 35.0 mm² | 6.544 mm | 115 A |
| 1/0 AWG | 53.49 mm² | 50.0 / 70.0 mm² | 8.252 mm | 150 A |
Under ASTM B258, conductor diameter in mm is d = 0.127 × 92^((36 - AWG)/39), and cross-sectional area is A (mm²) = (π / 4) × d².
12 AWG (3.31 mm²) should be replaced with 4 mm² metric wire, and 10 AWG (5.26 mm²) with 6 mm² metric wire.