Calculate how many solar panels you need, array peak power in kWp, inverter size and roof area from your monthly electricity bill in kWh.
Photovoltaic Standard (IEC 61724): Calculation accounts for a real-world system Performance Ratio (PR = 0.80) covering thermal, wiring and inverter losses.
| Potencia Campo (kWp) | Nº Paneles (500 Wp) | Inversor Nominal | Producción Anual Media | Superficie Mínima |
|---|---|---|---|---|
| 2,0 kWp | 4 paneles | 2,0 kW | 3.000 - 3.400 kWh/año | 9 m² |
| 3,0 kWp | 6 paneles | 3,0 kW | 4.500 - 5.100 kWh/año | 13 m² |
| 5,0 kWp | 10 paneles | 5,0 kW | 7.500 - 8.500 kWh/año | 22 m² |
| 8,0 kWp | 16 paneles | 8,0 kW | 12.000 - 13.600 kWh/año | 35 m² |
For DC and single-phase AC circuits, cross-sectional area S (mm²) = (2 × Length × Current × ρ) / Voltage Drop (V). Always verify that conductor ampacity meets NFPA 70 (NEC Table 310.16) or IEC 60364.
Under NEC and IEC standards, the recommended maximum voltage drop is 3% for branch circuits and 5% total for combined feeder and branch circuits.