Calculate room heating power in Watts and the number of radiator sections needed based on floor area, climate zone and water ΔT (EN 442).
Thermal Standard (EN 442 & ASHRAE): Radiator heat output drops non-linearly with lower water temperatures according to the exponent n ≈ 1.30.
| Climate Zone | Reference Climate Type | Well Insulated Home | Average / Older Insulation |
|---|---|---|---|
| Zona A / B | Mild Coastal / Mediterranean Climate | 65 W/m² | 80 W/m² |
| Zona C | Temperate Maritime / Oceanic Climate | 75 W/m² | 95 W/m² |
| Zona D | Cold Continental / Inland Plateau | 90 W/m² | 110 W/m² |
| Zona E | Severe Mountain / High Altitude (>800m) | 105 W/m² | 130 W/m² |
Depending on insulation and climate zone, rooms require 65 to 110 W/m². At standard boiler ΔT 50°C, a 60cm aluminum radiator section outputs ~125 W.
Under EN 442, heat output scales with (ΔT / 50)^1.3. Running a low-temperature heat pump at ΔT 30°C reduces radiator output by roughly 48%.